Footing Design Excel (Isolated Footing Combined Footing) Sheet Download

Footing Design Excel (Isolated Footing Combined Footing) Sheet Download


Types of Footing:

1. Isolated Footing:

An isolated footing is a type of foundation used for individual columns. They are generally square, rectangular, or round in shape to bear the load from a single column and spread this to the earth.

An isolated footing is a type of foundation used for individual columns. It is usually rectangular, square or circular in shape to take the load from one column and put it down on the soil.

When to Use: Isolated footings are suitable when there is a long way between columns, which are all loads able to be borne effectively by the soil beneath a building.

These footings are common in structures with widely spaced columns and strong soil conditions.

Design Considerations

During the design of an isolated footing, the following points need to be taken into consideration: The axial load carried by the column.

·      The bearing capacity of the soil.

·      The size and shape of the footing.

·      The depth necessary for stability

Example:

For a column with an axial load of 400 kN and a soil bearing capacity of 150 kN/m², the size of the footing can be calculated as follows:

1.    Determine the area of the footing:
The area of the footing can be found by dividing the load on the column by the bearing capacity of the soil.
Area of footing = 400 kN / 150 kN/m² = 2.67 m²

2.    Determine the side length (if footing is square):
To determine the side length of a square footing, take the square root of the area.
Side length = √2.67 = 1.63 m

Thus, the dimensions of the isolated footing are approximately 1.63 m x 1.63 m.


2.    Combined Footing

Definition: a kind of footing that been used for two or more columns are very close to each other and it is not practical to have individual footings. Their purpose is to have multiple columns sharing a load, which is distributed equally among them all.

Combined footings are appropriate when columns are located close to each other and the bearing capacities of the soil are low or varying. This kind of footing is often used in buildings where columns are close together because they want equal loads on all four corners (or sides) of the slab.

Design Considerations

Key factors: for designing a combined footing are:

·      The load from multiple columns.

·      The spacing between columns.

·      The soil's bearing capacity.

·      The shape and design of the footing (usually rectangular or trapezoidal)

 Example:

Consider two columns with loads of 400 kN and 600 kN, spaced 3 meters apart, and a soil bearing capacity of 150 kN/m². The total load on the combined footing is:

·      Determine the total load on the footing:
Total load = 400 kN + 600 kN = 1000 kN

·      Determine the area of the footing:
Area of footing = Total load / Bearing capacity of soil
Area of footing = 1000 kN / 150 kN/m² = 6.67 m²

·      Determine the dimensions of the footing:
Assuming the footing is rectangular, let’s assume the length of the footing is 4 meters.
Width of footing = Area of footing / Length of footing
Width of footing = 6.67 m² / 4 m = 1.67 m

Thus, the dimensions of the combined footing are approximately 4 meters by 1.67 meters.


3. Bi-axial footing

When two columns are subjected to loads in different directions (e.g. both along the x and y axes), a foundation can be called bi-axial footing. This type of footing must be designed to resist both axial loads and moments in two directions.

When to Use:

Bi-axial footings are commonly used when a column experiences both vertical and lateral loads. This type of footing is particularly useful in buildings with irregular layouts or where moments going in both directions (rather than only one of them) need to be accounted for during design.

Design Considerations:

For bi-axial foundations include: Axial loads from each column in both x and y directions Eccentric loads lead to bending moments The bearing capacity of soils The shape and the dimensions of the footing (that is, usually rectangular or trapezoidal, depending on each case)

 Example:

For two columns with loads of 400 kN and 600 kN, spaced 3 meters apart, and a soil bearing capacity of 150 kN/m², the total load on the footing is 1000 kN.

However, because of the bi-axial moments, the footing dimensions will be adjusted to accommodate bending in both the x and y directions.

The calculation for moment resistance and load distribution will guide the final dimensions of the footing, ensuring that both axial and moment loads are adequately supported.

 


                                                              UnZip PW: digitaldeni


Post a Comment

Previous Post Next Post