Electricity Specification for HT Line Extension and Transformer Installation

 1. General & Installation Criteria

All works must follow the mutually inclusive Technical Specifications and Construction Standards of the Nepal Electricity Authority (NEA) (2007 February). Line alignments must be as straight as possible to minimize stays.

Basic spans are set at 50–55m for 33 kV and 11 kV lines, and 35–50m for low voltage (LV) lines depending on the wire count. Prior to installation, old wooden poles must be dismantled.

Line clearances, optimum conductor sag, and safety rules must be strictly maintained. Break angles dictate whether HV pin insulators or disc insulator fittings (for dead ends) are used.

2. Stays & Transformer Structures

At least one stay must be installed for dead-end and tee-off structures, unless specific pole, span, and break-angle conditions remove the requirement. Transformer structures require two separate earth rods driven at least 2m from the pole and separated by 6m.

One rod grounds surge arresters/equipment, while the other grounds the low-voltage winding neutral, transformer body, and MCCB box. Copper circuit conductors must be placed below aluminum conductors to manage rainwater flow.

Transformers can only be charged after the Transformer Commissioning Report is approved.

3. Grounding Procedure

Grounding is mandatory for surge arrester studs, non-current carrying parts, and LV neutral points. The LV line neutral must be grounded every 15 poles. Specific conductor sizes are mandated (e.g., 2 AWG copper welded for surge arresters) and must be encased in rigid plastic pipes 3m above the pole foundation. Ground rods must be driven at least 40cm below grade.

4. Low Voltage Circuits & Miscellaneous Works

Bare 400/230V circuits utilize shackle insulators with D-irons, mounted on the side facing most house connections. Conductors require a 305mm spacing, arranged vertically from top to bottom as Red, Yellow, Blue, and Neutral.

Conductor stringing includes required fittings, with double disc insulators placed at extreme deviations. Tree trimming must be coordinated with the CBO, and all dismantled structures must be transported back to the site store.